Type E Full Face Isolation Gaskets
Full-face sealing for flat-face flanges
A Type E isolation gasket is a full-face gasket: the isolating element covers the entire flange face and the bolt holes pass through the gasket itself. Because the outside diameter matches the flange outside diameter and every bolt hole is gasketed, the Type E pattern seals the whole joint face rather than only a raised ring. It is the style normally specified when both flanges are flat face, where there is no raised face to locate a smaller gasket and no confined cavity to hold one in position.
In a Protek Type E assembly the gasket is only one part of the electrical break. Full-length insulating sleeves pass through the gasket holes and through the flange bolt holes, and isolating washers sit under each nut and bolt head, so no steel path connects the two flanges. The pattern is available across the Protek range: a rubber-faced phenolic retainer with a nitrile sealing element for economical Class 150–300 work (Scout), an incline-plane G10 or G11 retainer with a self-energizing Quad seal for general industrial duty (Delta), and a 316 stainless steel core with a mechanically retained PTFE spring-energized seal for critical service (Ranger), including the API 6FB fire-safe Ranger FS.
Because the gasket covers the bolt circle, the isolating washers sit on the gasket surface rather than on bare steel, so the washer outside diameter and the gasket hole spacing have to suit each other as well as the flange. That is one of the details a supplied kit resolves on the drawing before anything is manufactured.
Key features
- Full-face coverage — the gasket OD matches the flange OD and every bolt hole is isolated
- Bolt holes sized for full-length insulating sleeves, not just the stud diameter
- Phenolic, G10, G11 or 316 SS core constructions to match the service
- Nitrile, PTFE spring-energized and serrated PTFE sealing elements
- Sizes from 1/2" through 120" depending on product family
- Pressure classes from ANSI 150 to ANSI 2500 and API 2K to API 15K
- Isolating washers and steel backing washers supplied with the kit
Specifications
| Gasket style | Type E — full face, bolt holes through the gasket |
|---|---|
| Flange facing | Flat face (FF) |
| Outside diameter | Matches the flange outside diameter |
| Retainer | Phenolic · G10 · G11 · 316 SS core, by product |
| Sealing element | Nitrile · PTFE spring-energized · serrated PTFE (fire safe) |
| Size range | 1/2"–24" Scout · 1/2"–120" Delta · 1/2"–48" Ranger and Ranger FS |
| Pressure class | ANSI 150–300 Scout · 150–900 Delta · 150–2500 Ranger and Ranger FS |
| Temperature | Up to 392°F (200°C) for Ranger and Ranger FS |
| Bolting | Full-length sleeves with isolating washers on both sides |
| Documentation | Certificate of conformance as standard, MTRs on request |
| Origin | Manufactured in the US and internationally |
Construction data for the product family. Confirm the specific joint, medium and temperature with Protek Engineering before ordering.
Which Protek products
Typical applications
Flat-face piping
Joints where both flanges are flat face and a full-face gasket is the only pattern that seals the face.
Cathodically protected lines
Buried or submerged steel pipe where the flange must not short the coating system to a grounded structure.
Water and wastewater
Low and moderate pressure distribution, treatment and plant piping in ANSI 150–300 service.
Chemical and industrial plant
Process lines on flat-face valves, pumps and vessels where the medium is compatible with the retainer and seal.
Selection & installation notes
Sizing the bolt holes
The gasket holes must clear the insulating sleeve, and the sleeve must clear the flange bolt hole. Use the kit configurator to check sleeve and washer sizing against the actual flange dimensions before ordering.
Compression and bolt load
A full-face gasket is compressed over a larger area than a raised-face gasket, so the bolt load per unit sealing area is lower. Check the joint in the torque calculator and confirm the gasket seating stress is reached at the available bolt load.
Installation
Clean both faces, align the sleeve and washer stack on each stud, and tighten in a cross pattern in at least three passes. Verify electrical isolation after assembly, for example per NACE SP0286 practice, before the line is returned to service.
Check the joint with the engineering tools
Frequently asked questions
What is a Type E isolation gasket?
+−
A Type E is a full-face isolating gasket: its outside diameter matches the flange outside diameter and its bolt holes are covered, so the whole flange face is sealed and isolated. It is used on flat-face flanges.
Does a Type E gasket work without sleeves and washers?
+−
No. The gasket alone isolates the faces but leaves the studs and nuts as a metal path between the flanges. A Type E kit adds full-length sleeves and isolating washers so each stud is isolated from both flanges.
Can a Type E gasket be used on a raised-face flange?
+−
Type E is made for flat-face joints. On raised-face flanges the raised face contacts the gasket area inside the bolt circle, so the Type F pattern is the correct selection.
What sizes and pressure classes are available?
+−
Scout covers 1/2"–24" in ANSI 150–300, Delta 1/2"–120" in ANSI 150–900 / API 2K–5K, and Ranger and Ranger FS 1/2"–48" in ANSI 150–2500 / API 2K–15K.
Configure the kit for your flange
Build the gasket, sleeve and washer set for your flange and download the drawing and bill of materials, or send the service conditions to Protek Engineering for a written recommendation.